–67–
REGULATORY AGENCY STATEMENTS
The 5110XM may be used as a slave DACT providing central or remote station service for a central or
remote station listed local FACP. The 5110XM may also be used as a stand-alone local, central station or
remote station control. Some comments that apply to these installations are listed below:
When used as a slave DACT:
* Wire the 5110XM's hard-wired zones to the FACP alarm, supervisory and trouble contacts. Each
zone must have a 2k EOLR installed at the FACP. Program these zones for fire alarm (type 9), fire
supervisory (type 18) or trouble (type 19) response, respectively, as required.
* Both dialers must be used. Connect both dialers to seperate telephone lines and enable supervision
for each dialer.
* Program the 5110XM to send fire alarm, supervisory(if used), trouble, AC loss, low battery, normal
dialer test and off-normal dialer test reports. Program dialer test reports to be sent every 24 hours.
* Size the back up battery to provide 24 hour standby time for central station installation and 60 hour
standby time for remote station installations.
When used as a stand-alone control:
* wire fire alarm and sprinkler supervisory sensors to the 5110XM's hard wired zones. Each zone
must have a 2K EOLR installed at the last device on the zone wire run. Program these zones for the
required response.
* Mount one keypad within 3 feet of the control and run wires to the control in conduit.
* For local installations, wire polarized indicating devices to the bell output and enable the bell
supervision.
* For central and remote station installations, both dialers must be used. Connect both dialers to
seperate telephone lines and enable supervision for each dialer.
* Program the 5110XM to send fire alarm, supervisory (if used), trouble, AC loss, low battery, normal
dialer test and off-normal dialer test reports. Program dialer test reports to be sent every 24 hours.
* Size the back-up battery to provide 24 hour standby time for local and central station installations
and 60 hour standby time for remote station installations.
0FEDERAL COMMUNICATIONS COMMISSION (FCC) Part 15 STATEMENT
This equipment has been tested to FCC requirements and has been found acceptable for use. The FCC
requires the following statement for your information:
This equipment generates and uses radio frequency energy and if not installed and used properly, that is,
in strict accordance with the manufacturer's instructions, may cause interference to radio and television
reception. It has been type tested and found to comply with the limits for a Class B computing device in
accordance with the specifications in Part 15 of FCC Rules, which are designed to provide reasonable pro-
tection against such interference in a residential installation. However, there is no guarantee that
interference will not occur in a particular installation. If this equipment does cause interference to radio or
television reception, which can be determined by turning the equipment off and on, the user is encouraged
to try to correct the interference by one or more of the following measures:
• If using an indoor antenna, have a quality outdoor antenna installed.
• Reorient the receiving antenna until interference is reduced or eliminated.
• Move the radio or television receiver away from the receiver/control.
• Move the antenna leads away from any wire runs to the receiver/control.
• Plug the receiver/control into a different outlet so that it and the radio or television receiver are on
different branch circuits.
If necessary, the user should consult the dealer or an experienced radio/television technician for additional
suggestions. The user or installer may find the following booklet prepared by the Federal Communications
Commission helpful: "Interference Handbook"
This booklet is available from the U.S.. Government Printing Office, Washington, DC 20402.
The user shall not make any changes or modifications to the equipment unless authorized by the
Installation Instructions or User's Manual. Unauthorized changes or modifications could void the user's
authority to operate the equipment.