– 19–
15
16
ZONE 1
SMOKE
(+)
(-)
2 WIRE SMOKE
DETECTOR
2K
EOLR
ZONE 5
Figure 5: 2-Wire Smoke Detector Connected to Zone 5
COMPATIBLE 2-WIRE SMOKE DETECTORS
Detector Type Device Model #
Ionization, direct wire System Sensor 1100
Ionization with B110LP base System Sensor 1151
Ionization, direct wire System Sensor 1400
Ionization w/B401B base System Sensor 1451
Ionization duct detect. w/DH400 base System Sensor 1451DH
Photoelectric, direct wire System Sensor 2100
Photoelectric w/heat sensor, direct wire System Sensor 2100T
Photoelectric w/B110LP base System Sensor 2151
Photoelectric w/heat sensor, direct wire System Sensor 2300T
Photoelectric, direct wire System Sensor 2400
Photoelectric w/heat sensor, direct wire System Sensor 2400TH
Photoelectric w/B401B base System Sensor 2451
Photoelectric w/heat sensor & B401Bbase System Sensor 2451TH
Photoelectric duct detector w/DH400 base System Sensor 2451
Note: The above smoke detectors can be used together on zone 5.
Fire Alarm Verification for Smoke Detectors
This feature applies to 2-wire smoke detectors wired to zone 5 when zone 5 is set
to response type 16. This feature also applies to 4-wire smoke detectors wired to
any zone when the zone is set to response type 16 and the detectors are powered
from the Aux relay power output (field *34 must be set to 2).
The control will verify any alarm by resetting the smoke detectors after the first
alarm trigger and then waiting 90 seconds for a second alarm trigger. If the
smoke detector does not trigger again, the control will disregard the first trigger
and no alarm signal will occur. This feature eliminates false alarms due to
electrical or physical transients.
Turning Off Fire Alarm Sounding
You can turn off Fire alarm sounding by pressing the Silence/Reset key on the
control's pc board or by entering the user's code + OFF [1] key on any keypad. To
clear the "Alarm Silenced" message and to reset the detector's alarm, press the
Silence/Reset key or enter the User's Code + OFF again.