–44–
Press
*
47 SPLIT/DUAL REPORTING
Enter 0 to disable (Backup report only). This is the default.
TO PRIMARY TO SECONDARY
1 = Alarms, Restore Others
2 = All except Test Test
3 = Alarms, Restore All
4 = All except Test All
5 = All All
Press
*
49 PERIODIC TEST REPORT
Select the desired test report interval.
0 = none; 1 = 24 hours (default) ; 2 = weekly; 3 = 30 days.
Test Report Code entered in field
*
64 or
*
84 is sent.
Must be set to "1" for fire installations.
Press
*
50 SESCOA/RADIONICS SELECT
0 = Radionics (0–9, B–F reporting)
1 = SESCOA (0–9 only reporting)
Select 0 for all other formats. Default is 0.
Press
*
56 ZONE ASSIGNMENTS/ALARM REPORT CODES
Program response types and report codes for dialer
supervisory zones 11 and 12 as required.
TO PROGRAM
SYSTEM STATUS
AND RESTORE
REPORT CODES
(
*
58 –
*
74)
The following is a set of guidelines to be used for programming report codes.
The actual digits that you enter depend upon the particular installation, and
should be in agreement with you and the central station office receiving the
signals. Use these guidelines to program this entire section.
With a 3+1 or 4+1 Standard Format: Enter a code in the first box: 1–9, A,
B, C, D, E, or F. Enter "#+10" for A (this reports a “0” on some receivers),
"#+11" for B, "#+12" for C, "#+13" for D, "#+14" for E, "#+15" for F.
An entry of "0" in the first box will disable a report.
An entry of "0" in the second box will result in automatic advance to the
next field when programming.
With an Expanded or 4+2 Format: Enter codes in both boxes (1st and 2nd
digits) for 1–9, or A–F, as described above.
An entry of "0" in the first box will disable a report.
An entry of "0" in the second box will eliminate the expanded message for
that report.
With Ademco Contact ID Reporting: Enter a digit in the first box to
enable the zone to report. Use a different digit for each zone until you have
used up available digits. If the number of zones exceeds the number of
available digits, begin with digit 1 again. This is an "enabling" code only and
is not the actual code sent to the central station office. Entries in the second
boxes will be ignored. For system status (non-alarm) codes, enter a “1” in the
first box for all the system conditions you want to send to the central station.
An entry of "0" in the first box will disable the report.
In fire installations, you must program the control to transmit fire alarm, fire
supervisory (if used), trouble, AC loss, and both normal and off-normal dialer
test reports. In addition, test reports must be sent every 24 hours (program
field *49 = 1 (default).
Press *58 SUPERVISORY REPORT CODE |
This will be sent if a zone goes into a supervisory condition.
Press *59 SUPERVISORY RESTORE CODE |