–45–
This will be sent when the supervisory condition is restored.
Press *60 TROUBLE REPORT CODE |
This will be sent if a zone goes into trouble.
Press *61 BYPASS REPORT CODE |
This will be sent when a zone is manually bypassed.
Press *62 AC LOSS REPORT CODE |
Timing of this report is random within 6-12 hours after AC is lost.
If AC restores before the report goes out, there is no AC loss report.
Press
*
63 LOW BAT REPORT CODE |
This will be sent when a low battery condition exists in the
system’s standby battery.
Press
*
64 NORMAL TEST REPORT CODE |
This is sent periodically (* provided no trouble or supervisory
conditions exist; otherwise an Off-Normal Test code - as
programmed in *84 - will be reported) to test that the control and
phone lines are operational (frequency of report is selected in field
*49).
Press
*
69 GROUP RESTORES FOR TROUBLE and BYPASS
Enter 0 if a report is desired for each zone restoral, as it occurs.
This is the default. Enter 1 if a report is not desired until all
zones have restored.
Note: "1" not applicable to Contact ID reporting.
Press
*
70 ALARM RESTORE REPORT CODE, 1st DIGIT
This is sent when the zone that caused an alarm is restored to its
non-faulted condition. 2nd digit is automatically sent as the 2nd
digit of the zone alarm report code programmed in field
*56
, if
expanded or 4+2 reporting is selected.
Press
*
71 TROUBLE RESTORE REPORT CODE |
This is sent when a trouble in a zone is restored. Field *69 applies.
Press
*
72 BYPASS RESTORE REPORT CODE |
This is sent when a zone that has been bypassed is un-bypassed.
Field *69 applies.
Press
*
73 AC RESTORE REPORT CODE |
This is sent when AC power has been restored after an AC power
outage.
Press
*
74 LOW BAT RESTORE REPORT CODE |
This is sent when a system low battery condition is restored to
normal.
Press *79 MAIN/BACKUP DIALER ENABLE |
Enter [1] to enable or [0] to disable each dialer M B
(default = [1][1])
Press *84 MISCELLANEOUS REPORT CODES | | |
FIRE W/T FIRE W/T OFF-
START END NORM
TEST
Press
*
94 DOWNLOAD PHONE NUMBER
| | | | | | | | | | |
Enter up to 12 digits;
0–9, # +11 for “[*]”, # + 12 for “#”, # + 13 for a pause. Do not fill unused
spaces. End field by entering “
*
”. To clear entries, press
*94*
.