– 21 –
02 Report Code
1st 03 2nd 12 3C
The report code consists of 2 hexadecimal digits,
each in turn consisting of 2 numerical digits. For
example, for a report code of "3C", enter [0][3] for
"3" and [1][2] for "C". Refer to Section 11.
SYSTEM COMMUNICATION for complete
information on report codes, if necessary.
Enter the desired report code and then press [*] to
continue.
Typical summary display
Zn ZT RC
02 09 3C
A summary display will appear, showing the data
for the zone that was just programmed.
If it is programmed satisfactorily, press [*] to
continue.
Program Alpha?
0 = No 1 = Yes 0
The next request is to enter Alpha descriptors for
the zones. The entry may be done now (enter 1) or
may be done at a later time using *82 interactive
mode (enter 0). We recommend that the entry of
Alpha descriptors be done using *82 mode.
Enter Zn Num.
(00 = Quit) 02
If “0” (no) was entered above, the system will
return to the "Enter Zone Number" prompt.
Proceed with the programming for the next zone,
as indicated previously.
When you have programmed all the detection zones
satisfactorily, exit
*56
interactive mode at the
Enter Zn Num. prompt by pressing: [0] [0]
Then exit the programming mode by keying
*
99.
Proceed to the check-out procedure that follows.
Check-Out Procedure For Detection Zones
After installation of all devices is completed, the system should be checked, as
follows.
1. Make certain that all devices and sensors connected to the zones are not in
a faulted state.
2. Power up the control if you have not already done so..
3. After a 50 second delay, with all zones intact, the AC Power LED should be
ON and the warning buzzer should be OFF. If an optional Alpha keypad is
connected you should see the following display:
**** SYSTEM ****
**** NORMAL ****