– 16–
desired data, then press
[*]
plus the next data field number to be
programmed.
4. If you try to enter a non-existent field, the keypad will display EE or Entry
Error. Simply re-enter [*] plus a valid field number.
Reviewing a Data Field
Press [#] plus Field No. Data will be displayed for that field number. No
changes will be accepted in this mode.
Erasing an Entry in a Data Field
To delete an entry in a field, press [
*
] plus Field No. + [
*
]. (Applies only to
fields
*
40–
*
43, and
*
94).
Interactive Mode Programming (*56 and *82)
Typical prompt displayed
during interactive mode
programming
Enter Zn Num.
(00 = Quit) 01
Zone Number ↑
Press [
*
] plus interactive mode No. (for example,
*56
). The Alpha keypad
will display the first of a series of prompts requesting entries.
A detailed procedure (with displays of prompts) is provided in those sections
where programming in the interactive mode is to be performed.
Interactive Mode Used To Program
*56
Zone Programming Zone characteristics and report codes
*82
Alpha Programming Zone alpha descriptors
Loading Factory Defaults
To load the factory defaults, enter the programming mode, press *97
Do not press *97 to load defaults if any programming has been done
previously—data already programmed into the system will be changed!
*96 resets the Subscriber Account number and CSID in preparation for an
initial download. If using *96, it must be done after *97 if loading factory
defaults.
Exiting the Programming Mode
*99 allows re-entry into the program mode using Master Code + 8 0.
*98 inhibits re-entry into the programming mode using the Master code.