TOTAL STANDBY/ALARM LOAD WORKSHEETS
To calculate the total current for the Aux. power, bell & aux. relay outputs, multiply each device's standby
and/or alarm current by the number of units used.
1) Enter devices used on
aux. power output,
calculate standby and
alarm currents, then
add to get aux. power
current subtotal.
AUX. POWER OUTPUT Total Current
Device Model # Device Current X # of Units = Standby Alarm
Aux. Power Output Subtotal
(terminals 17 & 18) 350mA max 350mA max
Note: 6137/6137R Draws 85mA during alarm and 40mA during battery standby
6139/6139R Draws 100mA during alarm and 40mA during battery standby
2) Enter devices
connected to bell
output, calculate
alarm currents, then
add to get bell output
current subtotal.
BELL OUTPUT Total Current
Device Model # Device Current X # of Units = Standby Alarm
XXXXXX
XXXXXX
XXXXXX
XXXXXX
XXXXXX
Bell Output Subtotal XXXXXX (1.0 Amp
max)
3) Enter devices
connected to the aux.
relay output, calculate
standby and alarm
currents, then add to
get aux. relay output
current subtotal.
Note: No entries are
necessary when the red
relay power jumper (W3)
is cut.
AUX. RELAY OUTPUT Total Current
Device Model # Device Current X # of Units = Standby Alarm
Aux. Relay Output Subtotal (terminals 5, 6 or 7 & 18) (350 mA (1.0 Amp
max) max)