
– 11–
1. Make sure that the mounting screws are tight. This insures that there is a
good ground connection between the PC board and the cabinet.
2. Dress all wires away from microprocessor (the center section of the pc
board). Use the tie-wrap loops on the left and right sidewalls of the cabinet
for anchoring wires. This step is important for minimizing the risk of
control radio frequency interference (RFI) with television reception.
Standard Phone Line Connections
The 5110XM provides two supervised dialer outputs: the main dialer and the
back-up dialer. In fire installations, both outputs must be connected to
separate telephone lines providing loop start service.
Connect the main dialer and back-up dialer (if used) outputs to telephone
company lines using the RJ31X cables supplied. Do not connect to telephone
company lines which provide ground start service.
DO NOT connect both outputs to the same telephone line. A secondary phone
line is required in case of primary phone line failure.
1. WARNING! To prevent the risk of shock disconnect the telephone lines at
the telco jack prior to servicing this control.
2. If the control is connected to a PBX telephone line, make sure that the PBX
system has a backup power supply that can support it for at least 24 hours
(central station usage) or 60 hours (remote station usage). Many PBX
systems DO NOT have power backup and will cause communication
failures when power is lost.
Enabling the Dialer Outputs
To enable the dialer outputs, entries must be made in field *79. Enter 1 in the
first entry space to enable main dialer. Enter 1 in the second entry space to
enable backup dialer.
Telephone Line Supervision
The supervision circuits on both the main and backup dialer outputs will
indicate a fault when the tip/ring voltage falls below 2 volts, provided that their
supervisory zones are enabled (zones 11 and 12, respectively). These zones are
enabled in field *56 and should be assigned a response type of 19 (24-hr.
trouble).
In fire installations, both outputs must be configured for line
fault supervision.
Dialer Operation
When only the main dialer is enabled ([1,0] in field *79), the 5110XM will
attempt to route all calls over the main output. When both main and back-up
dialers are enabled ([1,1] in field *79), the 5110XM will attempt to route all
calls over the main output unless a fault is detected, at which time it will
attempt to use the back-up output. Line faults will light the line fault indicator
and, if a keypad is installed, will result in a zone 11 main dialer fault or zone 12
back-up dialer fault display. The control will make up to ten attempts to
transmit a report. (Ten attempts will be made to primary number when only
this number is programmed. Otherwise, five attempts will be made to the
primary number followed by five attempts to the secondary number when both
numbers are programmed.) After the tenth attempt, the control will hang-up
and will light the built-in Comm Fail indicator. A Comm Fail message with
also be displayed at the keypads (if installed).
Comentarios a estos manuales