Type 17
Fire Waterflow Alarm
Provides a fire alarm when zone is shorted for longer than the time
programmed in field *78 delay time setting. The combined sensor and
program field *78 delay must not exceed 90 seconds.
Provides either a trouble on an open circuit (field *32=0) or a supervisory
on open circuit (field *32=1).
Usually assigned to a zone containing a fire sprinkler waterflow sensor.
Bell output may be programmed to remain latched on alarm or to restore
when zone restores (see field *76).
Type 18
Fire Sprinkler
Supervisory
Provides a supervisory indication when a zone is shorted for longer than
the time programmed in field *78 delay time setting when delay is enabled
in field *57 . The combined sensor and program field *78 delay must not
exceed 90 seconds.
Provides either a trouble on an open circuit (field *32=0) or a supervisory
on an open circuit (field *32=1).
No bell output is is provided.
Usually assigned to a zone containing fire sprinkler supervisory sensors
such as Post-Indicator-Value sensors.
Assigned to a zone that is wired to a FACP supervisory contact
Type 19
24-Hr. Trouble
Provides a trouble response on an open or short circuit, and on system zone
faults.
Usually assigned to system zones such as Zone 10 (earth ground fault) and
Zone 11 (main dialer fault).
Assigned to a zone that is wired to a FACP trouble contact