Section 8: AUXILIARY RELAY CONNECTIONS
This section provides the following information:
General information about the auxiliary relay
Wiring the auxiliary relay
Programming the auxiliary relay
General Information
The 5110XM provides on auxiliary relay output which may be configured as one
of the following:
Wet 12VDC form C relay output
Dry, unsupervised form C relay output with contacts rated at 30VAC/VDC,
2A max. resistive loads
The relay (terminal 6) is set at the factory for a 12V nominal (10-14VDC)
output, providing 350mA max standby current/1A max alarm current.
The total standby current that can be drawn from the auxiliary relay and
auxiliary power outputs cannot exceed 350mA. The total alarm current that
can be drawn from these outputs plus the bell output cannot exceed 1A.
If configuring the relay as a dry, form C relay output, cut the red jumper
labeled W3 on the PC board. Zones programmed for non-fire related 24 hour
audible alarm response (type 07) must be programmed to activate the auxiliary
relay output and not the bell output.
Relay Connections
The figures below show how to wire the auxiliary relay output for unsupervised
alarm output and for 4-wire smoke detector power usage.
5
6
+
-
Note: The communicator provides 12VDC power
on terminal 6 when the red jumper (W3) is intact.
ALARM
AUX RELAY
FACTORY DEFAULTS
• Set for alarm activation (34=1)
• No zones trigger by default
(Must program 85, 86)
• 16 min. timeout(31=4)
NOTES:
• Use non-polarized indicating
devices
• Wiring is not supervised
• Take care not to exceed the
terminal 6 and overall system
alarm current ratings.
(1A max)
7
GROUND
N.O.
POLE
N.C.
Terminal 18
Note: The control provides 12VDC power on terminal
6 when the red jumper (W3) is intact
.
Figure 7: Wiring the auxiliary relay output for unsupervised alarm
output.
5
6
+
-
18
RESET
7
GROUND
POLE
N.C.
4-WIRE
SMOKE
DETECTOR
EOLR
EOLR RELAY
BRK A77-716B
-
+
TO
HARDWIRED ZONE (ZN 1-5)
Figure 8: Wiring the auxiliary relay output for 4-wire smoke
detector power usage.