Remote SAFEPATH Manual Sheet 12 of 50
Rev. C December 1998
Power Calculations
It is necessary to calculate the current draw for battery back-up requirements. The current requirements depend on the system
configuration and the options installed. The total current is the sum of the currents of all the components in the system. There are
two different system current ratings:
Standby Current
Alarm Current
Standby Current Calculations:
System Controller Board 150mA
Amplifier 1 See Note 1
Amplifier 2 See Note 1
Amplifier 3 See Note 1
Amplifier 4 See Note 1
Optional RMS-1 40mA (If Installed)
Optional Trouble Audible See Note 2
Optional SPL 40maA (If Installed)
________
Total:
Note 1: If no amplifier is installed in the slot then the current for that amplifier is zero. If there is an amplifier the standby current
depends on the model of the amplifier installed in the slot and the pre-selected 1 of 8 evacuation tones.
Model Standby Current Temporal Worst case
As per UL full power CODE-3 tone
SIN wave testing TONE HI/LO
SALL-15S 100mA 100mA 100mA
SAA10S/SE Series 240mA 125mA 150mA
SAA40S/SE Series 400mA 300mA 300mA
SAA80S/SE Series 600mA 300mA 400mA
Note 2: Use the rated current for the optional trouble audible attached to the system.
Alarm Current Calculations:
System Controller Board 150mA
Amplifier 1 See Note 4
Amplifier 2 See Note 4
Amplifier 3 See Note 4
Amplifier 4 See Note 4
Digital Voice See Note 5
Optional RMS-1 75mA (If Installed)
Optional Trouble Audible See Note 6
Zone 1 Strobes See Note 7
Zone 2 Strobes See Note 7
Zone 3 Strobes See Note 7
Zone 4 Strobes See Note 7
Optional SPL 190mA (If Installed)
________
Total: