P82467-001 L
Sheet 5 of 8
STEP 2:
Set desired alarm tone as follows (refer to Figure 3 and Table 5).
Multitone Appliances are field set for any one of eight alarm tones by setting a four-position switch (SW1) as shown in Figure 3
and Table 5. Use SW1 POS 2, 3, 4 to select the desired alarm tone (refer to Table 5 below).
Table 5: Alarm Tones
SW1
Switch Settings
Tone Pattern Description POS POS POS
2 3 4
Horn Broadband Horn (Continuous) 1 1 1
Bell 1560 Hz Modulated (0.07 Sec. ON/Repeat) 1 0 1
March Time Horn Horn (0.25 Sec. ON/0.25 Sec. OFF/Repeat) 0 0 1
Code 3 Horn Horn (ANSI S3.41 Temporal Pattern) 1 1 0
Code 3 Tone 500 Hz (ANSI S3.41 Temporal Pattern) 0 1 1
Slow Whoop 500-1200 Hz Sweep (4.0 Sec. ON/0.5 Sec. OFF/Repeat) 0 1 0
Siren 600-1200 Hz Sweep (1.0 Sec.ON/Repeat) 1 0 0
HI/LO 1000/800 Hz (0.25 Sec. ON/Alternate) 0 0 0
WIRING INFORMATION:
Figure 4:
Multitone Appliance Wiring Diagram
+
(+)
(-)
TO NEXT APPLIANCE OR
RESISTOR (EOLR)
FROM PRECEDING APPLIANCE OR
FIRE ALARM CONTROL PANEL (FACP)
END OF LINE
-
+
-
1. Strip leads 3/8 inches and connect to screw terminals. Multitone Appliances have in-out wiring terminals that accepts two
#12 to #18 American Wire Gauge (AWG) wires at each screw terminal.
2. Break all in-out wire runs on supervised circuits to assure integrity of circuit supervision. The polarity shown in the wiring
diagram is for operation of the appliances. The polarity is reversed by the Fire Alarm Control Panel (FACP) during
supervision
MOUNTING OPTIONS:
CAUTION: The following figures show the maximum number of field wires (conductors) that can enter the backbox used
with each mounting option. If these limits are exceeded, there may be insufficient space in the backbox to accommodate the
field wires and stresses from the wires could damage the product.
Although the limits shown for each mounting option comply with the National Electrical Code (NEC), Wheelock recommends
use of the largest backbox option shown and the use of approved stranded field wires, whenever possible, to provide additional
wiring room for easy installation and minimum stress on the product from wiring.